期刊文献+

架空导线线夹表面氧化分析及改进措施 被引量:6

Analyses and Improvement Measurements for Oxidation of Terminal Connector Used for Overhead Lines
在线阅读 下载PDF
导出
摘要 螺栓型双导线设备线夹,应用于某35kV变电站,巡视检查中发现其氧化腐蚀严重。采用宏观检验、化学成分分析、扫描电镜及能谱分析等手段对其进行分析检测。结果表明,线夹与铝导线接触面的接触电阻、线夹绝缘罩破损、水分和其他大气成分的腐蚀作用是线夹表面严重氧化腐蚀的外因;设备线夹选材不当,锌含量超标,是线夹形成点蚀形貌的内因,并最终造成线夹表面密集分布的腐蚀坑。提出控制线夹合金成分及含量、降低线夹与导线接触电阻、变电站巡视中注意检查绝缘罩严密性三项建议。 Terminal connectors for double conductors (bolted type) are used in 35 kV substation, severe oxidation corrosion was found during a routine inspection. The causes were studied by means of macrography, chemical composition analysis, SEM and energy spectrum analysis. The external causes made the terminal connector severely oxidized and corroded were contact resistance between connector and wires, damage of insulation cover, corrosion effect of rain water and other atmosphere composition. Improperly selected material for the terminal connector and excessive amount of Zn content were the internal causes of pitting corrosion and intensive distribution of etching pits on the surface of terminal connector. Some suggestions, such as controlling alloy composition and content, reducing the contact resistance between connector and wires, checking the tightness of insulation cover during substation routine inspection, were provided for safet operation of substation equipment.
出处 《腐蚀与防护》 CAS 北大核心 2012年第9期826-828,832,共4页 Corrosion & Protection
关键词 设备线夹 接触电阻 AL-ZN合金 点蚀 绝缘罩 安全运行 terminal connector contact resistance Al-Zn alloy pitting corrosion insulation cover safet operation
  • 相关文献

参考文献3

  • 1Graede T E. Corrosion mechanisms for aluminum ex- posed to the atmosphere[J]. Journal of the Electiomi cal Society, 1989,136(4) : 204.
  • 2Zhang X G. Corrosion and Electrochemistry of Zine [M]. New York:Plenum, 1996.
  • 3章小鸽.锌和锌合金的腐蚀(一)[J].腐蚀与防护,2006,27(1):41-50. 被引量:33

共引文献32

同被引文献60

引证文献6

二级引证文献45

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部