期刊文献+

热力站燃气供暖热水炉调峰效果及污染物排放 被引量:1

Peak Shaving Effect and Pollutant Emission of Gas-fired Heating and Hot Water Combi-boiler in Heating Station
在线阅读 下载PDF
导出
摘要 将济南某住宅小区作为研究对象,为满足严寒期供热需求,在热力站增设6台燃气供暖热水炉,用于调峰。实施调峰时,将部分热力站换热器出水引入热水炉进行二次加热,与未经热水炉二次加热的换热器出水混合后达到设定温度。在严寒期,对6台热水炉热效率、调峰效果、氮氧化物排放量进行实测计算与评价。热水炉正平衡热效率范围为95.62%~96.12%,反平衡热效率范围为96.70%~96.83%,二者非常接近。混水温度达到设计要求,说明热水炉的调峰效果良好。基准含氧量下一氧化氮质量浓度为18.75 mg/m^(3),低于DB 37/2374—2018《锅炉大气污染物排放标准》规定的排放限值。 Taking a residential area in Jinan as the research object,in order to meet the heating demand during the severe cold period,6 gas-fired heating and hot water combi-boilers were added in the heating station for peak shaving.When peak shaving is implemented,part of the effluent from the heat exchanger of the heating station is introduced into the combi-boilers for secondary heating,and it is mixed with the effluent from the heat exchanger that has not been reheated by the combi-boilers to reach the set temperature.During the severe cold period,the thermal efficiency,peak shaving effect and nitrogen oxides emission of 6 combi-boilers were measured,calculated and evaluated.The variation range of the positive equilibrium thermal efficiency of the combi-boilers is 95.62%-96.12%,and the variation range of the reverse equilibrium thermal efficiency is 96.70%-96.83%,both are very close.The mixed water temperature meets the design requirements,indicating that the peak shaving effect of the combi-boilers is good.The mass concentration of nitric oxide under the benchmark oxygen content is 18.75 mg/m^(3),which is lower than the emission limit stipulated in Emission Standard of Air Pollutants for Boilers(DB 37/2374-2018).
作者 林逸飞 田贯三 江悦悦 邰传民 王歆涛 LIN Yifei;TIAN Guansan;JIANG Yueyue;TAI Chuanmin;WANG Xintao
机构地区 山东建筑大学
出处 《煤气与热力》 2022年第8期17-20,共4页 Gas & Heat
关键词 燃气供暖热水炉 热力站调峰 热效率 氮氧化物 gas-fired heating and hot water combi-boiler heating station peak shaving thermal efficiency nitrogen oxides
  • 相关文献

参考文献3

二级参考文献27

  • 1盛晓文.换热器在热水网路中的变工况分析[J].哈尔滨建筑工程学院学报,1995,28(1):46-51. 被引量:2
  • 2秦冰,付林,江亿.利用系统热惯性的热电联产电力调峰[J].煤气与热力,2005,25(10):6-8. 被引量:20
  • 3韩伟国,江亿,郭非.多种供热供暖方式的能耗分析[J].暖通空调,2005,35(11):106-110. 被引量:38
  • 4由世俊,朱晏琳,郑雪晶,张欢.供热二级网侧设置燃气调峰锅炉的探讨及节能分析[J].暖通空调,2007,37(1):48-51. 被引量:14
  • 5Atli Benonysson, Benny Bohm, Hans F Ravn. Operational optimization in a district heating system[J]. Energy Conversion and Management, 1995, 36(5) : 297-314.
  • 6Hu Naiyi, Zhou Benping, Wang Weiqiao, et al. Energy and environmental conservation through district heating [J]. Energy Engineering: Journal of the Association of Energy Engineering, 2005, 102(1): 10-20.
  • 7Li Lianzhong, Zaheeruddin M. A control strategy for energy optimal operation of a direct district heating system [ J ]. International Journal of Energy Research, 2004, 28(7): 597-612.
  • 8Bvluev E D. Prospects for the development of centralized heat supply[ J ]. Thermal Engineering, 2001, 48 ( 11 ) : 932-937.
  • 9Henrik Madsen, Ken Sejling, Henning T Sogaard, et al. On flow and supply temperature control in district heating systems [J]. Heat Recovery Systems and CHP, 1994, 14(6) : 613-620.
  • 10Zhu Xueli, Qi Weigui, Ding Bao. A study of temperature control system based on DMC simplified algorithm[ C]// Proceedings of the Sixth International Conference on Electronic Measurement and Instruments. Taiyuan, China: Chinese Institute Electronics, Harbin Institute Technology, 2003: 2464-2467.