期刊文献+

频域谱技术用于油浸式电力变压器绝缘状态现场诊断 被引量:25

Application of Frequency Domain Spectroscopy to the Insulation Diagnosis of Oil-immersed Power Transformer on Site
在线阅读 下载PDF
导出
摘要 为了提高大型油浸式电力变压器的运行可靠性,提出了基于频域谱技术进行油浸式变压器绝缘状态及老化诊断的方法,利用该方法对国内某220kV变压器进行了测量,得到了其检修前后绝缘系统的介损频率特性曲线,并将频域谱测量方法与预防性试验数据进行了对比,验证了二者在变压器电容测量上的一致性。试验表明,频域谱方法可以反映变压器内部绝缘状态,估计固体绝缘中的含水量,为绝缘诊断提供参考信息;频域谱技术是一种无损试验方法,可作为现有绝缘诊断方法的重要补充,具有良好的应用前景。 In order to improve the reliability of large oil-immersed power transformers, the frequency domain spectroscopy for oil-immersed transformer insulation condition and aging diagnosis was introduced, a domestic 220 kV transformer was measured using FDS methods, and the tan δf curves of the transformer insulation system before and after maintenance were obtained and compared. The consistency of frequency domain spectroscopy and preventive test on measuring capacitance Was verified by comparing the data acquired by both methods. The results show that the frequency domain spectroscopy can reflect the internal transformer insulation, estimate moisture content in solid insulation, and provide reference information for the insulation diagnosis. FDS is a non-destructive testing method that can be used as a supplementary technique for the existing diagnosis methods, having good application prospects.
出处 《高电压技术》 EI CAS CSCD 北大核心 2009年第7期1648-1653,共6页 High Voltage Engineering
基金 国家高技术研究发展计划(863计划)(2007AA04Z411)~~
关键词 油浸式变压器 频域谱 绝缘 老化 含水量 介电响应 oil-immersed transformer FDS insulation aging moisture content dielectric response
  • 相关文献

参考文献7

二级参考文献33

  • 1钱政.大型电力变压器绝缘故障诊断中人工智能技术的应用研究[M].西安:西安交通大学,2000..
  • 2Wahab Mohamed A A, Hamada M M, Zeitoun A G et al. Novel modeling for the prediction of aged transformer oil characteristics[J]. Electric Power Systems Research, 1999, 51(1) : 61-70.
  • 3Benjisson C. Lifetime evaluation of transformers [J].CIGRE Electra.,1993,150;39-51.
  • 4Kachler A J. Diagnostic and monitoring technology for large power transformers[C]. CIGRE SC12,1997,Colloquium, Sydney, Australia.
  • 5Saha T K, Darveniza M, Hill D J T. Electrical and chemical diagnostics of transformer insulation[J]. IEEE Trans. Power Deliv., 1997, (12): 1547-1554.
  • 6Wang M. Review of condition assessment of power tranformers in service[J]. IEEE Elect. Insul. Magaz.,2002, 18(6): 12-22.
  • 7Jontscher A K. Universal dielectric response[J]. IEEE Elect. Insul. Magaz., 1990,(6):22-34.
  • 8Gubanski, SM. Dielectric response methods for diagnostic of power transformers [J]. IEEE Elect. Insul.Magaz., 2003,19(3): 12-18.
  • 9Kachler A J. Pro und contra einer vor-ort-prüfung vontransformatoren und drosselspulen[J]. HIGH VOLT 97,May 13-14, 1997, Dresden, Report 4.10.199-203.
  • 10Kachler A. J. Pro and contras of on-site tests on power transformers and reactors[C]. CIGRE 1998, SC12 paper No. 12-201:1-7.