基于频域介电谱的变压器油纸绝缘老化机理研究 被引量:9

Research on Transformer Oilpaper Insulation Aging Mechanism Based on Frequency Domain Spectrum
在线阅读 下载PDF
导出
摘要 基于频域介质响应的频域介电谱法是一种诊断电气设备绝缘状态的非破坏性方法。以变压器油纸绝缘结构为典型研究对象,采用扩展Debye等效电路模型,分析了绝缘老化引起的仿真模型中绝缘电阻、几何电容以及时间常数分支电路参数的变化,以及其对油纸绝缘系统主要参数如复电容和频域介电谱的影响规律,为频域介电谱法应用于油纸绝缘结构的电气设备老化状态检测提供重要的理论支持。研究结论可用于指导现场变压器的频域介电谱试验,并分析变压器油纸绝缘老化和受潮的状态。 Frequency domain spectrum (FDS) based on frequency domain medium response is a kind of non-destructive method to diagnose electrical equipment insulating state. The oilpaper insulation structure was taken as a typical study object and the expanded Debye equivalent circuit model was adopted. This paper analyzed the influence of insulation aging on insulation resistance, geometry capacitance and time constant etc branch circuit parameters variations in the simulation model, and on the oilpaper insulation system’s main parameters such as complex capacitance and FDS, to provide an important theoretical support for the application of FDS in the insulation aging state detection for the electrical devices of the oilpaper insulation structure. The conclusions can be used to guide onsite transformer FDS experiments and to analyze transformer oilpaper insulation aging and moisture status.
出处 《电工电气》 2012年第12期6-11,共6页 Electrotechnics Electric
关键词 变压器 频域介电谱 油纸绝缘 扩展Debye模型 绝缘老化 评估 transformer frequency domain spectrum oilpaper insulation expanded Debye model insulation aging evaluation
  • 相关文献

参考文献13

  • 1杨双锁,张冠军,董明,魏建林,王世强,于峥,冯玉昌.基于频域介电谱试验的750kV变压器绝缘状况评估[J].高压电器,2010,46(4):16-20. 被引量:20
  • 2Sumereder C,Muhr M.Dielectric Response Measurements at High Voltage Bushings[C]//International Conference on Condition Moni-toring and Diagnosis,2008.
  • 3Supramaniam G K,Hussien Z F,Aizam T M.Application of Frequency Domain Spectroscopy(FDS)in Assessing Dryness and Ageing State of Transformer Insulation Systems[C]//IEEE2nd International Conference on Power and Energy,2008.
  • 4Yew J H,Pradhan M K,Saha T K.Effects of Moisture and Temperature on the Frequency Domain Spectroscopy Analysis of Power Transformer Insulation[C]//IEEE Power Energy Society General Meeting——Conversion andDelivery of Electrical Engergy in the21st Century,2008.
  • 5吕玮,吴广宁,周利军,刘君,彭刚,高宗宝.采用介电频谱法分析评估油纸绝缘的微水质量分数[J].高电压技术,2010,36(12):3015-3020. 被引量:19
  • 6廖瑞金,郝建,杨丽君,梁帅伟,马志钦.变压器油纸绝缘频域介电谱特性的仿真与实验研究[J].中国电机工程学报,2010,30(22):113-119. 被引量:98
  • 7廖瑞金,马志钦,郝建,杨丽君,肖中男.水分对变压器油和绝缘纸频域介电谱特性的影响[J].高电压技术,2010,36(12):2869-2875. 被引量:47
  • 8Lundgard L E,Hansen W,Linhjell D,Painter T J.Aging of Oil-Impregnated Paper in Power Transformers[J].IEEE Transactions on Power Delivery,2004,19(1):230-239.
  • 9Task Force.Furanic Compounds Analysis:A Tool for Predictive Maintenance of Oil-Filled Electrical Equipment[J].Electra,1997,175:9-12.