期刊文献+

500kV输电铁塔塔材锈蚀原因分析 被引量:3

Analysis on corrosion of angle steel used for 500kV transmission tower
在线阅读 下载PDF
导出
摘要 利用宏观检验、化学成分分析、显微组织检验、力学性能试验、腐蚀产物SEM形貌及能谱分析等试验方法对某500kV输电铁塔塔材腐蚀损伤原因进行了试验分析。结果表明,该段塔材的镀锌防护层并未遭受腐蚀损伤,塔材锈蚀痕迹为附近其他金属部件发生锈蚀后随雨水流至其表面所致。 In this paper,the corroded angle steel used for 500kV transmission tower was investigated by means of macro-morphology inspection,chemical composition analysis,mechanical property test,scanning electron micrograph analysis,microstructure analysis and energy spectrum analysis.The result showed that the galvanized protective layer of the angle steel was well preserved without corrosion damage,and the corrosion spot on surface of the tower materail was caused by the corrosion of other metal parts nearby and then the rusting outcome flowed with rain water to its surface.
作者 史贤达 陈浩 乔欣 樊平成 白昊仑 SHI Xian-da;CHEN Hao;QIAO Xin;FAN Ping-cheng;BAI Hao-lun(Inner Mongolia Power Research Institute,Hohhot 010020,China;Inner Mongolia Enterprise Key Laboratory of High Voltage and Insulation Technology,Hohhot 010020,China)
出处 《内蒙古石油化工》 CAS 2021年第12期38-41,共4页 Inner Mongolia Petrochemical Industry
基金 内蒙古电力(集团)有限责任公司2019年科技计划项目(2019-102) 内蒙古电力(集团)有限责任公司2021年科技计划项目(2021-46)。
关键词 500kV输电铁塔 角钢 失效分析 预防措施 500kV transmission tower angle steel failure analysis preventive measure
  • 相关文献

参考文献14

二级参考文献116

共引文献99

同被引文献26

引证文献3

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部