期刊文献+

接触器长距离控制线路分析 被引量:6

Analysis on Long-distance Control Circuit of Contactor
在线阅读 下载PDF
导出
摘要 分析长距离控制线路电压降对接触器可靠吸合的影响,以及导线间电容电流对接触器可靠断开的影响,举例计算满足接触器吸合和断开要求的2.5 mm^2导线允许的AC 220V控制线路最大长度。提出当控制线路允许最大长度无法满足工程需求时的解决方案。 Both the influence of long-distance control circuit voltage drop on the reliable switching-on of contactor and that of capacitance current between conductors on the reliable switching-off of contactor are analyzed. The maximum length of the allowable AC 220V control circuit for 2.5 mm2 conductor satisfying contactor switching-on and switching-off requirements is calculated by an example. The solution is proposed in case the maximum allowable length of control circuit cannot meet the engineering requirements.
作者 郑凯 倪高俊
出处 《建筑电气》 2018年第2期17-20,共4页 Building Electricity
关键词 接触器 控制回路 吸合功率 保持功率 中间继电器 电压降 接触器可靠断开 接触器可靠吸合 contactor control circuit switching-on power retention power intermediaterelay voltage drop reliable switching-off ofcontactor reliable switching-oncontactor