摘要 本文提出了一种基于压差和水温的风机盘管水流量测量方法。首先对影响风盘阻抗S的因素进行理论分析,同时结合各影响因素进行试验研究,得到影响阻抗S的主要因素,推导出各因素影响条件下的阻抗S综合计算公式,最终根据风机盘管水侧压差△P、供水温度Tw得到水流量Q。此种方法可以在不增加风机盘管水侧测量阻力、测量仪表投入较低的情况下实现风机盘管水侧流量测量,既适合新建空调系统,又适合既有空调系统节能改造。 This article proposed a new measurement method for the fan coil water flow based on pressure and temperature. First of all, we have some theoretical analyses to influencing factors of fan coil impedance S, meanwhile, we carry out some experiments based on some factors which influence the impedance S, and we got the main factors influencing impedance. The last, we derived a comprehensive formula of impedance under the condition of the various factors influence. Finally when we get the experimental data, such as pressure Ap~, temperature Tw, we got water flow Q. This method can realize fan coil flow measurement on the water side in these cases of do not increase the fan coil resistance on the water side and lower investment of measuring instrument. Therefore, it is suitable for the new air conditioning system, and is suitable for existing air conditioning system energy saving transformation.
出处 《建筑热能通风空调》 2015年第4期1-5,46,共6页 Building Energy & Environment
基金 "十二五"国家科技计划课题(2011BAJ03B12-3 2013BAJ10B02-03) 国家自然科学基金面上项目(51378005)
关键词 风机盘管 水流量 压差 阻抗 试验 fan coil unit, water flow, differential pressure, impedance, experiment
  • 相关文献

参考文献11

二级参考文献40

  • 1孟华,龙惟定,王盛卫.以TRNSYS为平台的集中空调水系统数字仿真器的建立[J].暖通空调,2005,35(3):7-11. 被引量:6
  • 2彭海静.基于Excel求高次方程的解[J].计算机应用与软件,2006,23(2):142-144. 被引量:10
  • 3森村正直 山崎弘郎.传感器技术[M].北京:科学出版社,1988.40-96.
  • 4张威,陈海波.中文Microsoft OfficeXP完全手册[M].北京:北京希望电子出版社,2001.
  • 5Mamdani E H.Application of fuzzy algorithm for simple dynamic plant[J].Proc IEEE,1974,121(12):1585-1588.
  • 6李庆杨 王能超 易大义.数值分析[M].北京:清华大学出版社,施普林格出版社,2001..
  • 7Robert F B. Quartz capillary flow meter for gases. Review of Scientific Instruments, 2004,75 (3): 772 ~ 779
  • 8Pillow J J,Ljungberg H,Hulskamp G, et al. Functional residual capacity measurements in healthy infants:ultrasonic flow meter versus a mass spectrometer. F ur Respir J. 2004,23(5):763~768
  • 9Kaltsas G,Nassiopoulou A G. Gas flow meter for application in medical equipment for respiratory control:study of the housing.Sensors and Actuators A:Physical,2004,110(1):413~422
  • 10中国建筑科学研究院 中国建筑业协会建筑节能专业委员会.GB 50189-2005 公共建筑节能设计标准[S].北京:中国建筑工业出版社,2005..

共引文献69

同被引文献14

引证文献2

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部