摘要
同走廊架设多回交直流输电线路可节约土地资源,但多回交直流输电线路相互之间存在静电和电磁耦合。研究并行走廊内各回线路稳态感应有利于线路检修作业安全。通过电磁暂态计算程序建立湖州多回并行走廊内的6条超、特高压交直流输电线路计算模型,计算了特高压交流线路与超、特高压直流线路之间的耦合影响,分析了带电和停电检修作业时在交直流线路不同运行方式组合下各检修线路静电和电磁感应电压的幅值和分布。结果表明,湖州地区并行多回交直流线路之间稳态感应电压对目前规程规定的带电和停电检修作业方式和工具的影响可以不予考虑。
Erecting multi circuits of AC and DC transmission lines in the same corridor can save the land resources, however there are electrostatic and electromagnetic couplings among multi circuits of AC and DC transmission lines. It is favorable for the safety of maintenance operation of these transmission lines to research the steady-state induction voltage of transmission lines parallelly erected in the corridor. Through the calculation by electromagnetic transient program(EMTP), a computation model of six UHVAC and EHVDC/UHVDC transmission lines parallelly erected in the corridor located in Huzhou, Zhejiang province is established; the influence due to the coupling between UHVAC lines and EHVDC/UHVDC lines are calculated; the amplitudes and distributions of electrostatic induction voltages and electromagnetic induction voltages during the live-line overhaul and power-off maintenance under the combination of different operating modes of UHVAC and EHVDC/UHVDC lines are analyzed. Analysis results show that the influence of the steady-state induction voltage among parallelly erected multi circuits of AC and DC transmission line on the live-line overhaul and power-off maintenance modes and tools specified in current operating instruction can be neglected.
出处
《电网技术》
EI
CSCD
北大核心
2014年第8期2310-2314,共5页
Power System Technology
关键词
同走廊架设
特高压交、直流线路
线路检修作业
稳态感应电压
耦合
erected in the same corridor
UHV AC/DC transmission lines
line maintenance operation
steady induced voltage
coupling