基于包含谐波模型的加权最小二乘估计算法的电压暂降检测方法 被引量:7

Voltage sag detection based on weighted least-squares estimation algorithm with harmonic models
在线阅读 下载PDF
导出
摘要 针对动态电压恢复器需要以较快的速度检测出电网电压暂降,提出一种基于对电网电压建立谐波模型的加权最小二乘估计算法的电压暂降检测方法。通过重置协方差,在电网电压的谐波分量较高时该算法也能准确快速地判断出电压暂降。由于建立了谐波模型,稳态误差不会包含大量谐波分量,因此重置协方差的阈值可以设置得较小,使得该算法能够较快地检测出深度较小的电压暂降。通过设置不同的实验条件,验证了该算法具有良好的检测性能。 The dynamic voltage restorer should detect the grid voltage sag rapidly,for which,a detection method based on the weighted least-squares estimation algorithm with harmonic models is proposed. It detects the voltage sag accurately and rapidly by covariance resetting,even when the grid voltage contains considerable harmonic components. Since the harmonic models are built and the steady-state error contains only a few harmonic components,smaller covariance resetting threshold may be selected,which helps to rapidly detect low- depth voltage sags. Its better detection performance is verified under different experimental conditions.
出处 《电力自动化设备》 EI CSCD 北大核心 2013年第9期36-41,共6页 Electric Power Automation Equipment
关键词 动态电压恢复器 电压暂降检测 谐波模型 加权最小二乘法 重置协方差 dynamic voltage restorer voltage sag detection harmonic model weighted least-squaresestimation covariance resetting
  • 相关文献

参考文献6

二级参考文献56

  • 1李妍,余欣梅,熊信艮,段献忠.电力系统电压暂降分析计算方法综述[J].电网技术,2004,28(14):74-78. 被引量:53
  • 2万国成,任震,吴日昇,何毅思.混合法在复杂配电网可靠性评估中的应用[J].中国电机工程学报,2004,24(9):92-98. 被引量:79
  • 3尹忠东,李奇睿,韩民晓.考虑阻尼电阻影响的动态电压调节器线路侧滤波器的设计[J].电网技术,2004,28(20):64-67. 被引量:5
  • 4[1]Woodley N H, Morgan L. Sundaram A. Experience with an inverter-based dynamic voltage restorer[J]. IEEE Trans. on Power Delivery, 1999,14(3):1181-1186.
  • 5[2]Conrad L E, Bollen M H J. Voltage sag coordination for reliable plant operation[J]. IEEE Trans. on Industrial Application, 1997,33(6): 1459-1464.
  • 6[3]Masashi Oeno, Naoki Fukuzu, Nobuyuki Fujiwara, et al. Development and field Test of series Voltage compensator for power distribution system. [J].Proceedings of Japan Society of Electrical Engineering, part B, 2002,(8):90-95.
  • 7[7]Neil H. Woodley, Ashok Sundaram,Trevor Holden T.C. Einarson. Field experience with the new platform-mounted DVRTM [A]. Proceedings of POWERCON[C]. Australia, 2000: 1324-1328.
  • 8ZHAN Chang-jiang,RAMACHANDARAMURTHY K,ARULAMPALAM A,et al. Dynamic voltage restorer based on voltage-space-vector PWM control [J]. IEEE Trans Ind Applicat, 2001,37(6) : 1855-1863.
  • 9CHUNG Y,PARK Sang-young,MOON S L,et al. The control and analysis of zero sequence components in DVR system[A]. Power Engineering Society Winter Meeting [C]. Columbus,USA:IEEE,2001. 1021-1026.
  • 10ZHAN Chang-jiang,RAMACHANDARAMURTHY K,ARULAMPALAM A,et al.Dynamic voltage restorer based on voltage-space-vector PWM control[J].IEEE Trans.Ind.Applicat.,2001,37(6): 1855-1863.

共引文献351

同被引文献82

引证文献7

二级引证文献66

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部