期刊文献+

变电站蓄电池设备的选择及参数计算 被引量:4

Parameters Calculation and Type Choice of Battery Device in Transformer Substation
在线阅读 下载PDF
导出
摘要 根据某110 kV GIS变电站实际直流负荷情况,在采用阀控式密封铅酸蓄电池设备的基础上,对蓄电池的标称容量、数量、均衡充电电压、放电终止电压、高频开关充电装置模块参数选择进行详细计算,最终确定该变电站蓄电池配置设计方案,即容量200 Ah、数量106个,单体蓄电池均衡充电电压2.33 V、放电终止电压1.87 V,采用1组高频开关充电装置,并选取5个10 A的模块进行蓄电池充电。该设计方案可确保变电站直流系统的安全、稳定运行。 The paper introduces the detailed calculations of the battery nominal voltage, the number of battery, equalizing charge voltage, final discharging voltage, the parameter selection of high-frequency switch charger moduie according to DC load in some 110 kV GIS substation, based on a valve regulated sealed lead-acid battery. The result of calculation reaches the design, the battery normal capacity is 200 Ah, the number is 106, equalizing charge voltage 2.33 V and discharge charging device switching frequency charges for finish voltage 1.87 V the battery are used, per battery, and a 5 modules of 10 A are chosen. The scheme ensures the DC system in substation runing safely and stability.
出处 《内蒙古电力技术》 2013年第3期71-73,78,共4页 Inner Mongolia Electric Power
关键词 变电站 阀控式密封铅酸蓄电池 直流电源 持续放电容量 电压水平 高频开关充电装置 substation valve regulated sealed lead-acid battery direct current power supply continuous discharge capacity voltage level charging equipment of high frequencyswitching
  • 相关文献

参考文献4

二级参考文献6

  • 1DL/T5044-2004.电力工程直流系统设计技术规程.,..
  • 2电力工程直流系统设计手册(第二版)白忠敏/刘百震/於崇干.
  • 3瑞达阀控式密封铅酸蓄电池安装使用说明书.
  • 4DL/T5044—2004.电力工程直流系统设计技术规程[S].北京:中国电力出版社,2004.
  • 5国家电网公司.直流电源系统管理规范[Z].北京:中国电力出版社,2005.
  • 6电力系统用蓄电池直流电源装置运行与维护技术规程(DL/T 724-2000).

共引文献3

同被引文献31

引证文献4

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;