考虑污秽度及伞型结构影响的110kV支柱绝缘子交流闪络电压特性 被引量:3

AC Flashover Performance of Iced-covered 110kV Post Insulator Considering Its Pollution and Sheds Configuration
在线阅读 下载PDF
导出
摘要 支柱绝缘子覆冰后会使其电气绝缘性能显著下降,严重影响变电站的安全运行。为此,在人工气候室内开展了3种110kV支柱绝缘子在2种覆冰状态(L类、S类,圆柱形监测导体的冰厚分别为7mm、12mm)时交流覆冰闪络特性随染污盐密变化关系,及加装增爬型伞群后闪络电压的研究。结果表明:3种支柱绝缘子在S类覆冰状态时的最低冰闪电压间的差异很小,且防污型大伞径的支柱绝缘子的爬电距离不能充分利用;加装增爬型伞群后支柱绝缘子在相同覆冰状态和污秽的情况下50%闪络电压将明显提高。研究结果可为我国重覆冰地区采用增爬裙的支柱绝缘子提高变电站支柱绝缘配置和设计提供参考。 Based on measurements of AC flashover characteristics of three types of ice-covered post insulators in the multi-functional artificial climate chamber,we studied the relationships between icing flashover voltage and equivalent salt deposit densities under different icing states,respectively.When three kinds of post insulator sheds were ice bridges under serious icing states,the creepage distance of the anti-polluting post insulator can not be fully utilized,so the differences in minimum icing flashover voltage are very small for specimens.The 50% flashover voltage of the post insulator was significantly improved after installation the climbing umbrella group.The results can offer some references for the external insulation selection and design of transmission lines in the cold regions.
出处 《高电压技术》 EI CAS CSCD 北大核心 2012年第8期2037-2043,共7页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724501 2009CB724502) 国家创新研究群体基金(51021005)~~
关键词 支柱绝缘子 覆冰 交流闪络 染污盐密 电压特性 伞型结构 post insulator icing AC flashover equivalent salt depositdensity with stain voltage performance shed configuration
  • 相关文献

参考文献18

二级参考文献97

共引文献282

同被引文献47

  • 1蒋兴良,马俊,王少华,孙才新,舒立春.输电线路冰害事故及原因分析[J].中国电力,2005,38(11):27-30. 被引量:168
  • 2尚春.特高压输电技术在南方电网的发展与应用[J].高电压技术,2006,32(1):35-37. 被引量:71
  • 3Farzaneh M. Atmospheric icing of power networks[M].New York: Springer, 2008: 356-357.
  • 4Fikke S . Modem meteorology and atmosphericicing[C]//Proc 11th International Workshop onAtmospheric Icing of Structures(IWAIS 2005),Montreal,Canada, 2005.
  • 5Goodwin E J . Predicting ice and snow loads fortransmission lines[J]. Proceedings of the First IWAIS,1983,267-273.
  • 6Lee L Y, Nellis C L, Brown J E. 60 Hz tests on ice coated500kV insulator strings[C]//IEEE/PES Summer Meeting,San Francisco, USA,1975,Paper A75-499-4.
  • 7Sugawara N, Hokari K, Matsuoka R,et al. Insulationproperties of iced various insulators during freezing rainand de-icing[C]//Sixth International Symposium on HighVoltage Engineering,New Orieans. LA,USA* 1989:33-47.
  • 8IEEE Dielectrics and Electrical Insulation Society. IEEEStd. 1783-2009 IEEE guide for test methods andprocedures to evaluate the electrical performance ofinsulators in freezing conditions[S]. New York : TheInstitute of Electrical and Electronics Engineers,Inc.,2009.
  • 9Jiang X,Chao Y, Zhang Z,et al. DC flashoverperformance and effect of sheds configuration on pollutedand ice-covered composite insulators at low atmosphericpressnre[J] . IEEE Transactions on Dielectrics andElectrical Insulation, 2011,18(1): 97-105.
  • 10胡建林,罗明武,蒋兴良,等.不同试验方法下覆冰绝缘子直流闪络特性的比较[J].高电压技术,2012, 38(8): 2051-2058.

引证文献3

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部