摘要
在阻漏层概念的指导下 ,建立了 1∶1的模型。模型试验结果证实了理论上的预见 ,在高效过滤器不装在末端 (如当层高不够时 )而又有一定渗漏的情况下 ,新的末端将使室内含尘浓度降低 50 %~ 70 %。
Establishes the prediction of an air flow pattern based on a barrier layer concept with full scale modeling which shows that the new terminal combination can reduce the dust concentration indoor by 50% to 70% where the high efficiency filter is installed rather than onto the ceiling(as in the case of less floor height) and some leakage exists. Computer simulation also demonstrates good features of this air distribution form.
出处
《暖通空调》
EI
北大核心
2000年第3期1-7,共7页
Heating Ventilating & Air Conditioning