大型发电机定子绕组单相接地保护方式的商榷 被引量:6

Discussion on Single Phase Grounding Fault Protection Mode of Large-scale Generator Stator Winding
在线阅读 下载PDF
导出
摘要 发电机中性点不同接地方式当主变压器高压侧出现单相接地时,经变压器高低压绕组耦合传递至发电机机端基波零序电压值,经计算其值相差很大,理论分析计算和运行实践证明,汽轮发电机中性点经消弧线圈欠补偿接地方式的发电机基波零序过电压保护不宜动作于跳闸方式,如必须由信号改为跳闸方式,宜将消弧线圈欠补偿接地改为专用配电变压器高阻接地。 This paper has found that the zero sequence voltage conveyed from the primary and secondary side of the transformer to generator terminal is so different when a single-phase-to-earth occurs on the primary side of the transformer for a non-neutral-grounding generator. Based on the results of theoretical calculation and confirmation from the field operation, with the arc-suppression-soil-earth system, the generator' s first harmonic zero sequence over voltage protection will be not good for trip, if it must, then should be changed to trip from single, the grounding of arc-suppression reactor under compensation should be changed to the distribution transformer with high-impedance grounding.
出处 《电力系统自动化》 EI CSCD 北大核心 2006年第20期88-92,共5页 Automation of Electric Power Systems
关键词 定子单相接地保护 发电机中性点 消弧线圈接地 高阻接地 电场耦合 零序电压 stator single phase ground fault protection generator neutral arc-suppression-coil earth high-impedance ground electric field linkage zero sequence voltage
  • 相关文献

参考文献4

二级参考文献4

  • 1毕大强,王祥珩,余高旺,李德佳,王维俭.高准确度外加20 Hz电源定子单相接地保护的研制[J].电力系统自动化,2004,28(16):75-78. 被引量:33
  • 2[1]Brown P G, Johnson I B, Stevenson J R. Generator Neutral Grounding, Some Aspects of Application for Distribution Transformer with Secondary Resistor and Resonant Types.IEEE Trans on Power Apparatus and Systems, 1978, 97(3):683~695
  • 3王维俭(WangWeijian).电气主设备继电保护原理与应用(PrincipleandApplicationofElectricPowerEquipmentProtection),China Electric Power Press)[M].北京:中国电力出版社(Beijing,1998..
  • 4毕大强,王祥珩,王维俭.发电机中性点接地装置等效电路的分析[J].继电器,2003,31(1):12-16. 被引量:25

共引文献43

同被引文献20

引证文献6

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部