摘要 目的针对变流量空调水系统中末端盘管的热力特性,将调节阀特性与系统的可调节性能和稳定性综合考虑,讨论调节阀特性对系统调节性能的影响,为调节阀的选择提供理论依据.方法根据水系统中盘管热力特性与水流量之间的关系,正确选择调节阀的特性,使调节阀与末端装置组成的系统总的放大系数保持常数.结果得出调节阀影响变流量空调水系统可调节性的因素.结论变流量空调水系统的调节性能主要取决于系统供、回水温差与调节阀的阀权度.为使调节阀在工作环境下具有良好的调节特性,一方面应保证盘管的进出口温差,另一方面还应保证调节阀有足够的阀权度.调节阀的选择应以阀的流通能力为依据,而不应简单地根据管径粗略估选调节阀门. Based on the thermal characteristics of coil in VWV, the study considers regulating characteristics and stability, discusses regulating characteristics of regulating valve for hydraulic system and proposes the selection on regulating valve to variable water system. Based on the thermal characteristics of coil between heat transfer capacity and flow rate in hydraulic system, the study selects the property on regulating valve rightly, makes the general enlargement factor of system which is made up of the regulating valve and coil, maintain the constant. It concludes with the effect on regulating valve to regulating characteristics in variable flow system, and proposes the selection on regulating valve to variable water system. The regulating performance of variable flow water system is decided by supply, back water temperature and valve pressure drop. For the regulating characteristics in variable flow water system, on the one hand the water temperature difference ought to be guaranteed;on the other hand the regulating valve pressure drop is still made enough. The selection of regulating valve ought to be the foundation against the valve circulating capability, but not simply be picked up.
出处 《沈阳建筑大学学报(自然科学版)》 EI CAS 2006年第3期445-449,共5页 Journal of Shenyang Jianzhu University:Natural Science
基金 辽宁省教育厅基金项目(20202257)
关键词 变流量系统 热力特性 调节特性 阻力特性 variable flow hydraulic system thermal characteristics regulating characteristics resistance pressure characteristics
  • 相关文献

参考文献13

  • 1Hartman T. New Horizons for HVAC Control [J].Heating/Piping/Air Conditioning, 1995, 67(3):75-85.
  • 2Hartman T. Optimizing All - Variable Speed Systems with Demand Based Control[J]. The Automator, Automated Buildings, 2002 (3): 45-49.
  • 3江亿.管网可调性和稳定性的定量分析[J].暖通空调,1997,27(3):1-7. 被引量:46
  • 4Robert Petijean.水力管网全面平衡技术[M].郎四维译.北京:中国建筑工业出版社,1991.
  • 5高养田.空调交流量水系统设计技术发展[J].暖通空调,1996,26(3):20-26. 被引量:59
  • 6高养田.空调变流量水系统设计技术发展(续)[J].暖通空调,1996,26(4):29-35. 被引量:16
  • 7Avery G. Designing and Commissioning Variale Flow Hydronic System[J]. ASHRAE J, 1993 (7);45 -49.
  • 8Avery G. The Pros and Cons of Balacing a Variable Flow Water System[J]. ASHRAE J, 1990 (10): 30-59.
  • 9付祥钊 王岳人.流体输配管网[M].北京:中国建筑工业出版社,2002..
  • 10Hartman T. Design Issues of Variable Chilled Water Flow through Chillers [J]. ASHRAE. Trans. 1996(2):36-41.

二级参考文献3

  • 1高养田.空调交流量水系统设计技术发展[J].暖通空调,1996,26(3):20-26. 被引量:59
  • 2Rishel J B. The history of HVAC variable- speed pumping[J]. ASHRAE Trans, 1995(101): 1 - 12.
  • 3Franco W, Sen M, Yang K T. Modeling and control of a thermal - hydraulic network [ C ]. Anaheim California:ASME NHTC, 2001.

共引文献108

同被引文献28

  • 1陈盛.风机盘管节能设计与工程应用[J].暖通空调,2013,43(S1):238-243. 被引量:3
  • 2李彬,肖勇全,李震,冯晓梅.压差控制下VWV系统特性及节能分析[J].建筑热能通风空调,2005,24(1):44-47. 被引量:6
  • 3李彬,肖勇全,李德英,邵宗义.变流量空调水系统的节能探讨[J].暖通空调,2006,36(1):132-136. 被引量:18
  • 4周谟仁.流体力学泵与风机[M].北京:中国建筑工业出版社,1991..
  • 5Rishel J B. Twenty years' experience with variable speed pumps on hot and chilled water systems [ J ]. ASHRAE Transactions, 1998,94(2) :215 - 219.
  • 6Rishel J B. Control of variable - speed pumps on hot and chilled water systems [C ]. NY: AHRAE Transactions, 1991.
  • 7Larry Tillack, Rishel J B. Proper control of HVAC variable speed pumps [ J ]. ASHRAE Journal, 1998, 11:41 -47.
  • 8Rishel J B. Control of variable speed pumps for HVAC water systems [ J ]. ASHRAE Transactions, 2003,109:380 - 389.
  • 9Michel A B. Pumping energy and variable frequency drives[J]. ASHRAE Joumal, 1999,41 (12) : 37 - 38.
  • 10陈乃详,吴玉林.离心泵[M].北京:机械工业出版社,2003.