变质量体系能量转换及储存系统充能过程动态特性研究 被引量:1

Study of dynamic behavior of variable mass energy transformation and storage technology during energy charging process
在线阅读 下载PDF
导出
摘要 给出了变质量体系能量转换及储存技术的基本概念,讨论了在变质量体系能量转换及储存技术充能过程中因质量变化所产生的内部扰动的系统充能过程的动态特性。结果表明,当充能始、终溶液储罐内溴化锂质量分数差为0.11时,蓄能系统中仅用了一个0.6 m3的溶液储罐和一个0.17 m3的水储罐可储存109 kWh的制冷潜能,转移电网负荷23.3 kWh,蓄能系统运行的COP值可达到4.67。 A new technology of variable mass energy transformation and storage was proposed. The basic idea is to transfer the electric energy firstly into the chemical potential of working fluids and store as a form of the potential during off-peak time. Then the potential will be transformed into cold or heat energy needed during peak time. As there is only one working solution storage tank in the energy transformation and storage system, the mass of solution in the tank changes continuously during energy charging or discharging process, which makes the operation parameters of the system change. The dynamic behavior caused by internal turbulence because of the mass changing during energy charging process was studied and discussed. When the difference of the LiBr mass factor in the solution storage tank between the beginning and ending of the energy charging process is 0. 1, the energy transformation and storage system with a 0. 6 m3 solution storage tank and a 0. 17 m3 water storage tank can store up to about 109 kWh refrigerating potential and shift about 23. 3 kWh electric load in off-peak time. The COP of the system operation can be as high as 4. 67.
出处 《热科学与技术》 CAS CSCD 2004年第4期297-303,共7页 Journal of Thermal Science and Technology
关键词 变质量 能量转换 扰动 溶液 内部 蓄能 系统 COP值 溴化锂 制冷 energy transformation storage dynamic behavior
  • 相关文献

参考文献7

  • 1[3]BAHNFLETH, REINDL W P, DOUGLAS T.Prospects for cool thermal storage in a competitive electric power industry [J]. J of Architectural Eng,1999, 4(1):18-25.
  • 2[4]DINCER I. On thermal energy storage systems and applications in buildings [J]. Energy and Buildings,2002, 34(2): 377-388.
  • 3[5]SAITO A. Recent advances in research on cold thermal energy storage [J]. Int J Refirg, 2002,25(2): 177-189.
  • 4谢应明,梁德青,郭开华,樊栓狮,顾建明,陈晶贵.气体水合物蓄冷技术研究现状与展望[J].暖通空调,2004,34(9):25-28. 被引量:18
  • 5徐士鸣.蓄能技术新概念——制冷/制热潜能储存技术[J].电力需求侧管理,2003,5(1):43-48. 被引量:18
  • 6[8]徐士鸣,李维仲,张莉,等.制冷/制热潜能储存技术(2):以氨水为工质的潜能储存系统工作特性[C]∥第六届全国低温与制冷工程大会会议论文集.西安:西安交通大学出版社,2003:225-229.
  • 7[9]徐士鸣,李维仲,张莉.制冷/制热潜能储存技术(3):以溴化锂为工质的潜能储存系统工作特性[C]∥第六届全国低温与制冷工程大会会议论文集.西安:西安交通大学出版社,2003:230-234.

二级参考文献35

  • 1郭开华.气体水合及其在空调蓄冷技术中的应用[J].制冷,1994(2):22-28. 被引量:20
  • 2郭开华,舒碧芬.空调蓄冷及气体水合蓄冷技术[J].制冷,1995,14(4):15-21. 被引量:24
  • 3Dini S, Saniei N. Refrigerant hydrate as a cool storage medium. ASME, Heat Transfer Division, 1992, 215(8 - 13) : 63 - 72
  • 4方贵银.蓄冷空调工程实用新技术.北京:人民邮电出版社,2000
  • 5Dividson D W. Clathrate hydrates, water- a comprehensive treatise. Edited by Felix Franks. New York: Plenium Press, 1973
  • 6Tomlinson J J. Heat pump cool storage in a clathrate of freon. In: Proc of the 17th IECEC, 1982(4). 2060- 2064
  • 7Hiroshi K, Junjiro K. Feasibility of trichlorofluoromethane (CCl3, R11)heptadecahydrate as a heat storage raterial.Energy Convers Mgmt, 1985, 25(2): 179 - 186
  • 8Ternes M P. Studies on the R-12 gas hydrate formation process for heat pump cool storage application. In: Proc of DOE Physical and Chemical Energy Storage Annual Contractor's Review Meeting,1983
  • 9Mori Y H, Mori T. Formation of gas hydrate with CFC alternative R-134a. AIChE J, 1989, 35 (7):1227- 1228
  • 10Akiya T, Oowa M, Nakaiwa M, et al. Novel cool storage system using HCFC-141b gas clathrate. In:Proc of the 26th IECEC,1991 (6). 115 - 119

共引文献34

同被引文献18

引证文献1

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部