期刊文献+
共找到6篇文章
< 1 >
每页显示 20 50 100
VSG-based Adaptive Droop Control for Frequency and Active Power Regulation in the MTDC System 被引量:19
1
作者 Ren Wang Laijun Chen +1 位作者 Tianwen Zheng Shengwei Mei 《CSEE Journal of Power and Energy Systems》 SCIE 2017年第3期260-268,共9页
In this paper,a VSG(virtual synchronous generator)-based method with adaptive active power and DC voltage droop is proposed for the control of VSC stations in the multi-terminal DC(MTDC)system.This control strategy ca... In this paper,a VSG(virtual synchronous generator)-based method with adaptive active power and DC voltage droop is proposed for the control of VSC stations in the multi-terminal DC(MTDC)system.This control strategy can improve the inertial level of the AC networks and attenuate the rate of change of frequency when a disturbance occurs.In addition,the droop control of the active power and DC voltage is implemented to make the AC networks share the unbalanced power in the MTDC.The droop coefficients are adaptively adjusted depending on the frequency margin of every AC network,which makes the allocation of unbalanced power among AC networks more reasonable from the frequency variation perspective.The control strategy is evaluated in the scenarios of sudden load change and wind turbine tripping,and the results are presented to demonstrate its effectiveness. 展开更多
关键词 Adaptive droop control frequency regulation MTDC unbalanced power allocation virtual inertial
原文传递
Power quality enhancement in islanded microgrids via closed-loop adaptive virtual impedance control 被引量:7
2
作者 Yang Wang Junmiao Tang +3 位作者 Jiandong Si Xianyong Xiao Peter Zhou Jinshuai Zhao 《Protection and Control of Modern Power Systems》 SCIE EI 2023年第1期163-179,共17页
The high proportion of nonlinear and unbalanced loads results in power quality issues in islanded microgrids.This paper presents a novel control strategy for harmonic and unbalanced power allocation among distributed ... The high proportion of nonlinear and unbalanced loads results in power quality issues in islanded microgrids.This paper presents a novel control strategy for harmonic and unbalanced power allocation among distributed genera-tors(DGs)in microgrids.Different from the existing sharing strategies that allocate the harmonic and unbalanced power according to the rated capacities of DGs,the proposed control strategy intends to shape the lowest output impedances of DGs to optimize the power quality of the microgrid.To achieve this goal,the feasible range of virtual impedance is analyzed in detail by eigenvalue analysis,and the findings suggest a simultaneous adjustment of real and imaginary parts of virtual impedance.Because virtual impedance is an open-loop control that imposes DG to the risk of overload,a new closed-loop structure is designed that uses residual capacity and absorbed power as feedback.Accordingly,virtual impedance can be safely adjusted in the feasible range until the power limit is reached.In addi-tion,a fuzzy integral controller is adopted to improve the dynamics and convergence of the power distribution,and its performance is found to be superior to linear integral controllers.Finally,simulations and control hardware-in-the-loop experiments are conducted to verify the effectiveness and usefulness of the proposed control strategy. 展开更多
关键词 Islanded microgrid Harmonic power Unbalanced power Residual capacity Adaptive virtual impedance
原文传递
Power and Voltage Control Based on DC Offset Injection for Bipolar Low-voltage DC Distribution System
3
作者 Xinyi Kong Jianwen Zhang +4 位作者 Jianqiao Zhou Jiajie Zang Jiacheng Wang Gang Shi Xu Cai 《Journal of Modern Power Systems and Clean Energy》 SCIE EI CSCD 2023年第5期1529-1539,共11页
The bipolar low-voltage DC(LVDC) distribution system has become a prospective solution to better integration of renewables and improvement of system efficiency and reliability. However, it also faces the challenge of ... The bipolar low-voltage DC(LVDC) distribution system has become a prospective solution to better integration of renewables and improvement of system efficiency and reliability. However, it also faces the challenge of power and voltage imbalance between two poles. To solve this problem, an interface converter with bipolar asymmetrical operating capabilities is applied in this paper. The steady-state models of the bipolar LVDC distribution system equipped with this interface converter in the gridconnected mode and off-grid mode are analyzed. A control scheme based on DC offset injection at the secondary side of the interface converter is proposed, enabling the bipolar LVDC distribution system to realize the unbalanced power transfer between two poles in the grid-connected mode and maintain the inherentpole voltage balance in the off-grid mode. Furthermore, this paper also proposes a primary-side DC offset injection control scheme according to the analysis of the magnetic circuit model, which can eliminate the DC bias flux caused by the secondaryside DC offset. Thereby, the potential core magnetic saturation and overcurrent issues can be prevented, ensuring the safety of the interface converter and distribution system. Detailed simulations based on the proposed control scheme are conducted to validate the function of power and voltage balance under the operation conditions of different DC loads. 展开更多
关键词 Bipolar low-voltage DC distribution system interface converter DC offset injection unbalanced power voltage balance
原文传递
Elimination of Partial Overloading of Generators Under Unbalanced Operating Conditions of Power Systems
4
作者 Sudhakar Reddy Sama Subrata Paul Sunita Halder Nee Dey 《CSEE Journal of Power and Energy Systems》 SCIE 2016年第1期81-87,共7页
Unbalanced operating condition in a power system can cause partial overloading of the generators in the network,a condition where one or two of the three phases of the generator become overloaded even if the total 3-p... Unbalanced operating condition in a power system can cause partial overloading of the generators in the network,a condition where one or two of the three phases of the generator become overloaded even if the total 3-phase power output of the generator is within its specified limit.Partial overloading of generators beyond certain limits is undesirable and must be avoided.Distribution systems are often subjected to highly unbalanced operating conditions.Introduction of distributed generations(DGs),therefore,has rendered today’s distribution systems quite susceptible to this problem.Mitigation of this problem requires the issue to be addressed properly during analysis,operation and planning of such systems.Analysis,operation and planning of power networks under unbalanced operating condition require 3-phase load flow study.The existing methods of 3-phase load flow are not equipped to take into account any limit on the loadings of the individual phases of the generators.In the present work,a methodology based on NewtonRaphson(N-R)3-phase load flow with necessary modifications is proposed.The proposed methodology is able to determine the safe loading limits of the generators,and,can be adopted for operation and planning of power networks under unbalanced operating conditions to overcome the above difficulties.Test results on IEEE-37 bus feeder network are presented to demonstrate the effectiveness of the proposed method. 展开更多
关键词 Newton Raphson 3-phase load flow partial overloading of generators unbalanced operating condition of power systems
原文传递
Linear OPF-based Robust Dynamic Operating Envelopes with Uncertainties in Unbalanced Distribution Networks
5
作者 Bin Liu Julio H.Braslavsky Nariman Mahdavi 《Journal of Modern Power Systems and Clean Energy》 SCIE EI CSCD 2024年第4期1320-1326,共7页
Dynamic operating envelopes(DOEs),as key enablers to facilitate distributed energy resource(DER)integration,have attracted increasing attention in the past years.However,uncertainties,which may come from load forecast... Dynamic operating envelopes(DOEs),as key enablers to facilitate distributed energy resource(DER)integration,have attracted increasing attention in the past years.However,uncertainties,which may come from load forecasting errors or inaccurate network parameters,have been rarely discussed in DOE calculation,leading to compromised quality of the hosting capacity allocation strategy.This letter studies how to calculate DOEs that are immune to such uncertainties based on a linearised unbalanced three-phase optimal power flow(UTOPF)model.With uncertain parameters constrained by norm balls,formulations for calculating robust DOEs(RDOEs)are presented along with discussions on their tractability.Two cases,including a 2-bus illustrative network and a representative Australian network,are tested to demonstrate the effectiveness and efficiency of the proposed approach. 展开更多
关键词 Distributed energy resource(DER) dynamic operating envelope(DOE) feasible region robust optimisation uncertainty modelling unbalanced optimal power flow
原文传递
Loadability Assessment and Enhancement in Unbalanced Distribution Systems 被引量:1
6
作者 Arjun Tyagi Ashu Verma Pradeep R.Bijwe 《CSEE Journal of Power and Energy Systems》 SCIE 2018年第4期524-532,共9页
Voltage stability is a major concern in heavily loaded distribution networks.Careful determination of control parameters for loadability enhancement may maximize the utilization of distribution networks.In applicable ... Voltage stability is a major concern in heavily loaded distribution networks.Careful determination of control parameters for loadability enhancement may maximize the utilization of distribution networks.In applicable studies,most of the approaches optimize real/reactive power losses for the current operating conditions of the distribution network.Although,these types of approaches increase the stability margin,such an increase may not be sufficient.The most important factor in loadability enhancement is representation of future load scenarios in addressing the optimization problem.In this paper a look ahead approach is developed for loadability enhancement of an unbalanced distribution system.The determination of the critical loading point is conventionally done using continuation power flow,which is computationally very demanding,and also complex for implementation in unbalanced distribution networks.Therefore,a new,computationally very efficient voltage stability indicator is developed here for determination of the loadability limit.The proposed methodology is demonstrated on IEEE 4 bus and 25 bus unbalanced distribution systems with different transformer connections. 展开更多
关键词 LOADING stability margin voltage stability indicator unbalanced power flow
原文传递
上一页 1 下一页 到第
使用帮助 返回顶部